AC surge protector for LED Lighting system Class 1

MLPC1-230L-R
Part Number: 831211
MLPC1-230L-R
  • Type 2 (or 3) surge protectors for LED
  • Class 1
  • Very compact
  • Plate mounting
  • Spring terminal connection
  • Status indicator
  • Disconnection AC end of life
  • EN 61643-11 compliance

The MLPC range is a comprehensive series of AC surge protectors dedicated to LED lighting system. The MLPC are very compact to be integrated into luminaires and are available 2 modes of connection (screw terminal or spring).


SPD type
2 (or 3)
Network
220-240 V Single-phase
AC system
TT-TN
Max. AC operating voltage
Uc 320 Vac
Max. load current
IL 5 A
Temporary Over Voltage (TOV) Charasteristics - 5 sec.
Without disconnection
UT 335 Vac withstand
Temporary Over Voltage (TOV) Charasteristics - 120 mn
Without disconnection or with safety disconnection
UT 440 Vac disconnection
Temporary Over Voltage N/PE (TOV HT)
Without disconnection or with safety disconnection
UT 1200 V/300A/200 ms disconnection
Residual Current
Leakage current to Ground
Ipe None
Nominal discharge current
15 x 8/20 µs impulses
In 5 kA
Max. discharge current
max. withstand @ 8/20 µs by pole
Imax 10 kA
Total Maximum discharge current
max. total withstand @ 8/20 µs
Imax Total 20 kA
Withstand on Combination waveform IEC 61643-11
Class III test: 1.2/50µs - 8/20µs
Uoc 10 kV
Withstand on overvoltages IEEE C62.41.1
10 kV / 10 kA
Protection mode(s)
Common/Differential mode
Protection level L/N
@ In (8/20µs)
Up L/N 1.5 kV
Protection level L/PE
@ In (8/20µs)
Up L/PE 1.5 kV
Admissible short-circuit current
Isccr 10 000 A
Technology
MOV+GDT
Connection to Network
2 spring terminals opposite side in/out - wire 1.5mm² max.
Mounting
On plate
Housing material
Thermoplastic UL94 V-0
Operating temperature
Tu -40/+85°C
Protection rating
IP20
Failsafe mode
Disconnection and AC line cut-off
Disconnection indicator
LED green OFF and AC network cut-off
Voltage/operating indicator
Green Led ON
Dimensions
See diagram
Weight
0.035 kg
Standards compliance
EN 61643-11 / IEC 61643-11
Certification
CB Tested /IMQ
Thermal disconnector
Internal
Installation ground fault breaker
Type 'S' or delayed