Type 2+3 PV surge protector - VG and CTC Technology

DPVN40CVGS-21Y-1500
Part Number 65122103
DPVN40CVGS-21Y-1500

NEW CITEL PV SPD

  • Type 2+3 surge protector for Photovoltaic
  • CTC Technology
  • VG Technology
  • Discharge currents Imax/Itotal: 40/60 kA (8/20µs)
  • Common/Differential mode protection
  • Remote signaling
  • IEC 61643-31, EN 61643-31, EN 50539-11, UL1449 ed.5 compliance
  • Certified EN 61643-31 and IEC 61643-31

The DPVN40VG is CITEL's new series of type 2+3 SPDs for photovoltaic applications. The development of these SPDs is based on two technologies, patented exclusively by CITEL. The VG Technology guarantees total absence of leakage current and maximum reliability. Using CTC Technology, the DPVN40VG incorporates a thermosensitive separation point placed at the center of the SPD, guaranteeing the safest disconnection on the market. The products are designed for DIN rail mounting. Compact and equipped with a fault indicator, these products are easy to install and maintain.

Select another reference:

SPD type
2+3
Network
PV 1500 Vdc
Nominal PV voltage
Uocstc 1250 Vdc
Max. PV operating voltage
Ucpv 1500 Vdc
Residual Current
Leakage current to Ground
Ipe None
PV Permanent Operating current
Current consumption at Ucpv
Icpv None
Follow current
If None
Nominal discharge current
15 x 8/20 µs impulses
In 20 kA
Max. discharge current
max. withstand @ 8/20 µs by pole
Imax 40 kA
Total Maximum discharge current
max. total withstand @ 8/20 µs
Imax Total 60 kA
Withstand on Combination waveform IEC 61643-11
Class III test: 1.2/50µs - 8/20µs
Uoc 6 kV
Current withstand short circuit PV
Iscpv 15 000 A
Connection mode(s)
+/-/PE
Protection mode(s)
Common/Differential mode
Protection level +/-
@ In (8/20µs)
Up 4.8 kV
Protection level +/PE (-/PE)
@ In (8/20µs)
Up 4.8 kV
Protection level at 5 kA
@ 5 kA (8/20µs)
Up 4,0 kV
Protection level at Uoc
@ Uoc (1.2/50 µs)
Up 3,5 kV
Technology
VG Technology (MOV+GSG)
Connection to Network
By screw terminals: 2.5-25mm² (35mm²) / by bus
Format
Compact monobloc box
Plugable
No
Mounting
Symmetrical rail 35 mm (EN 60715)
Housing material
Thermoplastic UL94 V-0
Operating temperature
Tu -40/+85°C
Protection rating
IP20
Outdoor application
No
Failsafe mode
All pole disconnection from PV network
Disconnection indicator
1 mechanical indicator - Red/Green
Remote signaling of disconnection
Output on changeover contact
Max. Voltage/Current for remote signaling
250 V / 0.5 A (AC) / 30 V / 3 A (DC)
Dimensions
See diagram - 2.5TE (EN43880)
Weight
0.290 kg
Standards compliance
IEC 61643-31 / EN 61643-31 / EN 50539-11 / UL1449 ed.5
Certification
KEMA
Thermal disconnector
CTC Technology integrated
Back-up protection device
Without