DC power surge protector

DDC50S-21Y-1500
Part Number 828511663
DDC50S-21Y-1500
  • DC power Type 2 SPD
  • For Energy Storage/EV Charging
  • In/Imax: 20/50 kA
  • Pluggable modules
  • Remote signaling
  • prIEC 61643-41 compliance

The DDC50S-21Y range is type 2 pluggable surge protectors designed for protection to Energy System Storage (ESS). Its technology based on high energy varistor equipped with thermal disconnection mechanism offers protection efficiency and and a maximal reliability. These DC power surge protectors are available with a Max. DC operating voltage from 500 to 1500 Vdc. To ensure maximum protection of the ESS installation, CITEL has developed a kit (article code: 1156339601) of products consisting of a DDC50S-21Y surge protector and a specific fuse (100,000 A tested and approved) compatible with: short-circuits of storage systems and CITEL surge protectors.


SPD type
IEC

2

Nominal DC voltage
Un-dc

1200 Vdc

Max. DC operating voltage
Uc

1500 Vdc

Residual Current
Leakage current to Ground
Ipe

< 0.2 mA

Nominal discharge current
15 x 8/20 µs impulses
In

20 kA

Max. discharge current
max. withstand @ 8/20 µs by pole
Imax

50 kA

Impulse current by pole
max. withstand 10/350µs by pole
Iimp

4 kA

Protection level +/-
@ In (8/20µs)
Up

5.1 kV

Admissible short-circuit current
Isccr

100 000 A

Connection to Network

By screw terminals: 2.5-25 mm² (35 mm² rigid)

Plugable

Yes

Mounting

Symmetrical rail 35 mm (EN 60715)

Housing material

Thermoplastic UL94 V-0

Operating temperature
Tu

-40/+85°C

Protection rating

IP20

Failsafe mode

Disconnection from DC network

Disconnection indicator

1 mechanical indicator by pole - Red/Green

Spare module(s)

MDDC50-1500

Remote signaling of disconnection

output on changeover contact

Wiring for remote signaling

1.5 mm² max.

Max. Voltage/Current for remote signaling

250 V / 0.5 A (AC) / 30 V / 3 A (DC)

Dimensions

See diagram - 3 TE (EN43880)

APPLICATION

ENERGY STORGAGE SYSTEMS (ESS) /EV CHARGING

Standards compliance

prIEC 61443-41 - IEC61643-11

Thermal disconnector

Internal

Back-up protection device

50 A min. (Isccr 100 kA) - 125 A max. (Isccr 50 kA) - gBat Fuses