Type 1+2 AC surge protector - Single Phase
DAC1-13VG-11-320
Part Number: 821730332
- Type 1 + 2 + 3 AC surge protector
- VG Technology
- In : 20 kA
- Iimp : 12,5 kA on 10/350µs impulse
- No leakage current
- Pluggable module for each phase
- Remote signaling (option)
- Optimized to TOV
- EN 61643-11, IEC 61643-11 certified
- UL1449 ed.4 compliance
The DAC1-13VG is an extreme duty pluggable Type 1+2+3 SPD designed to protect AC powerline at the main switchboard of an installation equipped with lightning rod.
Equipped with exclusive CITEL’s VG technology, the range achieves an high protection level, guaranteeing a maximum protection efficiency, a absence of follow and leakage currents, a simplification of use (no additional lightning arrester required) and a maximum lifetime.
The DAC1-13VG surge protectors are especially compact and available in multipolar versions to protect single or 3-phase AC networks, which makes them the best surge protection solution for Type 1 requirements.
Select another reference:
- DAC1-13VG-10-150
- DAC1-13VG-10-275
- DAC1-13VG-10-320
- DAC1-13VG-11-150
- DAC1-13VG-11-275
- DAC1-13VG-11-320
- DAC1-13VG-20-150
- DAC1-13VG-20-275
- DAC1-13VG-20-320
- DAC1-13VG-30-150
- DAC1-13VG-30-275
- DAC1-13VG-30-320
- DAC1-13VG-31-150
- DAC1-13VG-31-275
- DAC1-13VG-31-320
- DAC1-13VG-40-150
- DAC1-13VG-40-275
- DAC1-13VG-40-320
SPD type | 1+2+3 | |
Network | 230 V single-phase | |
AC system | TT-TN | |
Max. AC operating voltage | Uc | 320 Vac |
Temporary Over Voltage (TOV) Charasteristics - 5 sec. | UT | 335 Vac withstand |
Temporary Over Voltage (TOV) Charasteristics - 120 mn | UT | 440 Vac withstand |
Temporary Over Voltage N/PE (TOV HT) | UT | 1200 V/300A/200 ms withstand |
Residual Current | Ipe | None |
Follow current | If | None |
Nominal discharge current | In | 20 kA |
Max. discharge current | Imax | 50 kA |
Total Maximum discharge current | Imax Total | 100 kA |
Impulse current by pole | Iimp | 12.5 kA |
Total lightning current | Itotal | 25 kA |
Withstand on Combination waveform IEC 61643-11 | Uoc | 6 kV |
Specific energy by pole | W/R | 40 kJ/ohm |
Protection mode(s) | L/N and N/PE | |
Protection level L/N | Up L/N | 1.5 kV |
Residual voltage L/N at 5 kA | Up-5kA | 0.9 kV |
Protection level N/PE at 5 kA | Up-5kA | 0.9 kV |
Admissible short-circuit current | Isccr | 50 000 A |
Technology | VG Technology (MOV+ GSG) | |
SPD configuration | Single phase | |
Connection to Network | By screw terminals: 2.5-25 mm² (35 mm² rigid) | |
Format | Plug-in modular box | |
Mounting | Symmetrical rail 35 mm (DIN 60715) | |
Housing material | Thermoplastic UL94 V-0 | |
Operating temperature | Tu | -40/+85°C |
Protection rating | IP20 | |
Failsafe mode | Disconnection from AC network | |
Disconnection indicator | 1 mechanical indicator by pole - Red/Green | |
Spare module(s) | MDAC1-13VG-320 + MDAC1-25G-xxx | |
Remote signaling of disconnection | option DAC1-13VGS-11-320: output on changeover contact | |
Wiring for remote signaling | 1.5 mm² max. | |
Max. Voltage/Current for remote signaling | 250 V / 0.5 A (AC) / 30 V / 3 A (DC) | |
Dimensions | See diagram - 2TE (EN43880) |
Standards compliance | IEC 61643-11 / EN 61643-11 / UL1449 4ed. | |
Certification | KEMA / EAC |
Thermal disconnector | Internal | |
Installation ground fault breaker | Type 'S' or delayed | |
Fuses | 125 A min. - 315 A max. - Fuses Type gG |