Smart SPD Monitoring Device
LSCM-D/24/P1000
LSCM-D/24/P1000
Part Number: 793532
  • Lightning and Surge Current Counter & SPD monitoring device
  • Wide surge current detection range:
    • 0.3/25 KA or 1/50 kA @10/350µs
    • 0.3/50 kA or 1/100 kA @ 8/20 µs
  • Front display for access to recorded events and device parameters
  • Peak current and time stamping recording of the surge currents
  • RS485 communication interface / MODBUS protocol
  • Monitoring features : 2 inputs (SPD or disconnector status) / 1 ouput
  • IEC62561-6 compliance

Lightning counters are designed to detect and record the impulse current conducted by the down conductor of the lightning protection system or by the earthing wire of a protective surge protection. This unit is useful to assess the stress of the protection devices, in order to perform their efficient maintenance.


Nominal line voltage Un 24 Vdc / 24 Vac
Max. AC operating voltage Mcov 24 Vac
Max. DC operating voltage Uc 24 Vdc
Connection mode(s) 2 connection PE ports
Minimum current sensibility Itc 1000 A
Max. admissible impulse current Imcw 100 kA (8/20µs) / 50 kA (10/350 µs)
Voltage measurement error 0.1 kA, +/- 5%
Wiring Connection wire sensor : Coaxial-cable AWG26
Mounting Symmetrical rail 35 mm (EN60715)
Housing material Thermoplastic UL94-V0
Operating and storage temperature -20/+60°C / -25 /+70°C
Protection rating IP20
Connection - Counter : Spring-cage terminals - Sensor : Plug-in (1 sensor line port)
Remote signaling of disconnection Two channel to input switching signal and one channel of output switching signal
Display 128*64 lattice OLED display, green/red status LED display
Dimensions See diagram
Weight 0.164 kg
Standards compliance EN 62561-6