Type 1+2+3 AC surge protector - Single phase

DACN1-35VGS-20-440
Part Number 29322022
DACN1-35VGS-20-440
  • Type 1+2+3 AC surge protector
  • VG Technology
  • In: 35 kA
  • Iimp: 35 kA on 10/350µs impulse
  • No leakage current
  • Unpluggable module for each phase
  • Remote signaling
  • Optimized to TOV
  • EN 61643-11, IEC 61643-11 complied

The DACN1-35VG is an extreme duty Type 1+2+3 SPD designed to protect AC powerline at the main switchboard of an installation equipped with lightning rod. Equipped with exclusive CITEL’s VG technology, the range achieves an high protection level, guaranteeing a maximum protection efficiency, a absence of follow and leakage currents, a simplification of use (no additional lightning arrester required) and a maximum lifetime.


SPD type
IEC

1+2+3

AC system

TN

Max. AC operating voltage
Uc

440 Vac

Max. load current @25°C
IL

100 A

Temporary Over Voltage (TOV) Characteristics - 5 sec.
Without disconnection
UT

580 Vac withstand

Temporary Over Voltage (TOV) Characteristics - 120 mn
Without disconnection or with safety disconnection
UT

770 Vac disconnection

Residual Current
Leakage current to Ground
Ipe

None

Follow current
If

None

Nominal discharge current
15 x 8/20 µs impulses
In

35 kA

Max. discharge current
max. withstand @ 8/20 µs by pole
Imax

70 kA

Impulse current by pole
max. withstand 10/350µs by pole
Iimp

35 kA

Withstand on Combination waveform IEC 61643-11
Class III test: 1.2/50µs - 8/20µs
Uoc

6 kV

Specific energy by pole
max. withstand 10/350 µs
W/R

306 kJ/o

Protection level
@ In (8/20µs) and @ 6 kV (1,2/50 µs)
Up

1.8 kV

Admissible short-circuit current
Isccr

50 000 A

Technology

VG Technology (MOV+GSG)

SPD configuration

Single phase

Connection to Network

By screw terminals: 2.5-25mm² (35mm² rigid)

Format

1-pole modular box assembled

Plugable

No

Mounting

Symmetrical rail 35 mm (EN 60715)

Housing material

Thermoplastic UL94 V-0

Operating temperature
Tu

-40/+85°C

Protection rating

IP20

Failsafe mode

Disconnection from AC network

Disconnection indicator

1 mechanical indicator by pole - Red/Green

Remote signaling of disconnection

Output on changeover contact

Wiring for remote signaling

1.5 mm² max.

Max. Voltage/Current for remote signaling

250 V / 0.5 A (AC) / 30 V / 3 A (DC)

Dimensions

See diagram - 4TE (EN43880)

Weight

0.836 kg

Standards compliance

EN 61643-11 / IEC 61643-11

Certification
Thermal disconnector

Internal

Installation ground fault breaker

Type 'S' or delayed

Back-up protection device

Fuses type gG - 315 A