Type 1+2 AC surge protector - 1-pole

DACN1-35VGS-10-440
Part Number 29321022
DACN1-35VGS-10-440
  • Type 1+2+3 Single phase AC surge protector
  • VG Technology
  • In: 35 kA
  • Iimp: 35 kA on 10/350µs impulse
  • No leakage current
  • Unpluggable module for each phase
  • Remote signaling
  • Optimized to TOV
  • EN 61643-11, IEC 61643-11 complied

The DACN1-35VG is an extreme duty Type 1+2+3 SPD designed to protect AC powerline at the main switchboard of an installation equipped with lightning rod. Equipped with exclusive CITEL’s VG technology, the range achieves an high protection level, guaranteeing a maximum protection efficiency, a absence of follow and leakage currents, a simplification of use (no additional lightning arrester required) and a maximum lifetime.


SPD type
1+2+3
Max. AC operating voltage
Uc 440 Vac
Max. load current
@25°C
IL 100 A
Temporary Over Voltage (TOV) Characteristics - 5 sec.
Without disconnection
UT 580 Vac withstand
Temporary Over Voltage (TOV) Characteristics - 120 mn
Without disconnection or with safety disconnection
UT 770 Vac disconnection
Residual Current
Leakage current to Ground
Ipe None
Follow current
If None
Nominal discharge current
15 x 8/20 µs impulses
In 35 kA
Max. discharge current
max. withstand @ 8/20 µs by pole
Imax 70 kA
Impulse current by pole
max. withstand 10/350µs by pole
Iimp 35 kA
Withstand on Combination waveform IEC 61643-11
Class III test: 1.2/50µs - 8/20µs
Uoc 6 kV
Specific energy by pole
max. withstand 10/350 µs
W/R 306 kJ/o
Protection level
@ In (8/20µs) and @ 6 kV (1,2/50 µs)
Up 1.8 kV
Admissible short-circuit current
Isccr 50 000 A
Technology
VG Technology (MOV+GSG)
SPD configuration
Single phase
Connection to Network
By screw terminals: 2.5-25mm² (35mm² rigid)
Format
1-pole modular box
Plugable
No
Mounting
Symmetrical rail 35 mm (EN 60715)
Housing material
Thermoplastic UL94 V-0
Operating temperature
Tu -40/+85°C
Protection rating
IP20
Failsafe mode
Disconnection from AC network
Disconnection indicator
1 mechanical indicator by pole - Red/Green
Remote signaling of disconnection
Output on changeover contact
Wiring for remote signaling
1.5 mm² max.
Max. Voltage/Current for remote signaling
250 V / 0.5 A (AC) / 30 V / 3 A (DC)
Dimensions
See diagram - 2TE (EN43880)
Weight
0.421 kg
Standards compliance
EN 61643-11 / IEC 61643-11
Certification
Thermal disconnector
Internal
Installation ground fault breaker
Type 'S' or delayed
Back-up protection device
Fuses type gG - 315 A