2-pair DIN rail plug-in Data surge protector
DLA2-48DBC
DLA2-48DBC
Part Number: 640314
  • Din rail plug-in surge protector
  • 2-pair
  • Un: 48 V
  • Shield wire protection
  • Without line cut-off
  • IEC 61643-21 compliance
  • UL497A
CITEL_Certif_SIL_DLA_DLA2_DLAH_DLU_DLU2_DLUH_DLC.pdf Installation Sheet

DLA2 surge protectors are designed to protect, against surge voltages due to lightning, terminals equipment connected to industrial buses, telecom lines or datalines. These surge protectors must be installed on symmetrical DIN rail and are available for most of the transmission lines: line voltage from 6 to 170V, bitrate up to 10 Mbit/s. These products are 2-pair surge protectors with removable module for easy maintenance.

Select another reference:

Network Fipway, WorldFIP, FieldBus-h2
Nominal line voltage Un 48 V
Max. DC operating voltage Uc 53 V
Max. load current IL 300 mA
Max. frequency f max. > 20 MHz
Insertion loss < 1 dB
Max. discharge current Imax 20 kA
Line inductance No
Protection mode(s) Common/Differential mode
Protection level Up 75 V
Max. capacitance C < 50 pF
Impulse current Iimp 5 kA
Nominal discharge current In 5 kA
Line/Line Nominal discharge current In L/L 5 kA
Line/Ground Nominal discharge current In L/PE 5 kA
Line resistance < 4.7 Ohm
Technology GDT+Clamping diode
SPD configuration 2-pair + shielded
Connection to Network screw terminal - cross section 0.4-1.5 mm²
Format Plug-in DIN box
Mounting Symmetrical rail 35 mm (EN60715)
Housing material Thermoplastic UL94-V0
Operating temperature -40/+85°C
Protection rating IP20
Failsafe mode Short-circuit - transmision cut-off - fault mode 2
Disconnection indicator Transmission interrupt
Spare module(s) DLA2M-48dBC
Remote signaling of disconnection No
Dimensions See diagram
Weight 0.063 kg
Standards compliance IEC 61643-21 / EN 61643-21 / UL497A
Certification UL listed