Type 2+3 PV surge protector - CTC Technology

DPVN40CS-21Y-1200
Part Number 65112102
DPVN40CS-21Y-1200

NEW CITEL PV SPD

  • Type 2+3 surge protector for Photovoltaic
  • CTC Technology
  • Discharge currents Imax/Itotal: 40/60 kA (8/20µs)
  • Common/Differential mode protection
  • Remote signaling
  • IEC 61643-31, EN 61643-31, EN 50539-11, UL1449 ed.5 compliance
  • Certified EN 61643-31 and IEC 61643-31

The DPVN40 is CITEL's new series of type 2+3 SPDs for photovoltaic applications. Based on CITEL's patented CTC Technology, the DPVN40 incorporates a thermosensitive separation point placed at the center of the SPD guaranteeing the safest disconnection on the market. The products are designed to be mounted on a DIN rail. Compact and equipped with a failure indicator, these products are easy to install and maintain.


SPD type
IEC

2+3

Network

PV 1000 Vdc

Nominal PV voltage
Uocstc

1000 Vdc

Max. PV operating voltage
Ucpv

1200 Vdc

Residual Current
Leakage current to Ground
Ipe

< 0.2 mA

PV Permanent Operating current
Current consumption at Ucpv
Icpv

< 0.1 mA

Follow current
If

None

Nominal discharge current
15 x 8/20 µs impulses
In

20 kA

Max. discharge current
max. withstand @ 8/20 µs by pole
Imax

40 kA

Total Maximum discharge current
max. total withstand @ 8/20 µs
Imax Total

60 kA

Withstand on Combination waveform IEC 61643-11
Class III test: 1.2/50µs - 8/20µs
Uoc

6 kV

Current withstand short circuit PV
Iscpv

15 000 A

Connection mode(s)

+/-/PE

Protection level +/-
@ In (8/20µs)
Up

4.3 kV

Protection level +/PE (-/PE)
@ In (8/20µs)
Up

4,1 kV

Protection level at 5 kA
@ 5 kA (8/20µs)
Up

3,5 kV

Protection level at Uoc
@ Uoc (1.2/50 µs)
Up

3,1 kV

Technology

MOV

Connection to Network

By screw terminals: 2.5-25mm² (35mm²) / by bus

Format

Compact monobloc box

Plugable

No

Mounting

Symmetrical rail 35 mm (EN 60715)

Housing material

Thermoplastic UL94 V-0

Operating temperature
Tu

-40/+85°C

Protection rating

IP20

Failsafe mode

All pole disconnection from PV network

Disconnection indicator

1 mechanical indicator - Red/Green

Remote signaling of disconnection

Output on changeover contact

Max. Voltage/Current for remote signaling

250 V / 0.5 A (AC) / 30 V / 3 A (DC)

Dimensions

See diagram - 2.5TE (EN43880)

Standards compliance

IEC 61643-31 / EN 61643-31 / EN 50539-11 / UL1449 ed.5

Certification

KEMA

Thermal disconnector

CTC Technology integrated

Back-up protection device

Without