2 (or 3)
230/400 V 3-phase
IT
440 Vac
580 Vac withstand
770 Vac disconnection
< 1 mA
None
5 kA
20 kA
15 kA
10 kV
1.5 kV
100 000 A
MOV
3-phase
By screw terminals: 2.5-25mm² (35mm² rigid)
Plug-in modular box
Yes
Symmetrical rail 35 mm (EN 60715)
Thermoplastic UL94 V-0
-40/+85°C
IP20
Disconnection from AC network
1 mechanical indicator by pole - Red/Green
MDACF15-440
output on changeover contact
1.5 mm² max.
See diagram - 1TE (EN43880)
0.319 kg
IEC 61643-11 / EN 61643-11 / UL1449 ed.5
Internal
Type 'S' or delayed
internal (equivalent AC rating : 25 A, gG Type)