Type 1+2+3 AC surge protector - Single phase

DAC1-13VG-40-320
Part Number: 821730314
DAC1-13VG-40-320
  • Type 1 + 2 + 3 AC surge protector
  • VG Technology
  • In : 20 kA
  • Iimp : 12.5 kA on 10/350µs impulse
  • No leakage current
  • Pluggable module for each phase
  • Remote signaling (option)
  • Optimized to TOV
  • EN 61643-11, IEC 61643-11 certified
  • UL1449 ed.5 compliance

The DAC1-13VG is an extreme duty pluggable Type 1+2+3 SPD designed to protect AC powerline at the main switchboard of an installation equipped with lightning rod. Equipped with exclusive CITEL’s VG technology, the range achieves an high protection level, guaranteeing a maximum protection efficiency, a absence of follow and leakage currents, a simplification of use (no additional lightning arrester required) and a maximum lifetime. The DAC1-13VG surge protectors are especially compact and available in multipolar versions to protect single or 3-phase AC networks, which makes them the best surge protection solution for Type 1 requirements.

Select another reference:

SPD type
1+2+3
Network
230/400 V 3-phase+N
AC system
TNS
Max. AC operating voltage
Uc 320 Vac
Temporary Over Voltage (TOV) Charasteristics - 5 sec.
Without disconnection
UT 335 Vac withstand
Temporary Over Voltage (TOV) Charasteristics - 120 mn
Without disconnection or with safety disconnection
UT 770 Vac withstand
Residual Current
Leakage current to Ground
Ipe None
Follow current
If None
Nominal discharge current
15 x 8/20 µs impulses
In 20 kA
Max. discharge current
max. withstand @ 8/20 µs by pole
Imax 50 kA
Total Maximum discharge current
max. total withstand @ 8/20 µs
Imax Total 200 kA
Impulse current by pole
max. withstand 10/350µs by pole
Iimp 12.5 kA
Total lightning current
max. total withstand @ 10/350µs
Itotal 50 kA
Withstand on Combination waveform IEC 61643-11
Class III test: 1.2/50µs - 8/20µs
Uoc 6 kV
Specific energy by pole
max. withstand 10/350 µs
W/R 40 kJ/ohm
Protection mode(s)
L/PE and N/PE
Protection level L/PE
@ In (8/20µs) and @ 6 kV (1,2/50 µs)
L/PE 1.5 kV
Protection level N/PE
@ In (8/20µs) and @ 6 kV (1,2/50 µs)
Up N/PE 1.5 kV
Protection level N/PE at 5 kA
@ 5 kA (8/20µs)
Up-5kA 0.9 kV
Residual voltage L/PE at 5 kA
@ 5 kA (8/20µs)
Up-5kA 0.9 kV
Admissible short-circuit current
Isccr 50 000 A
Network type
AC
Technology
VG Technology (MOV+GSG)
SPD configuration
3-phase+Neutral
Connection to Network
By screw terminals: 2.5-25mm² (35mm² rigid)
Format
Plug-in modular box
Plugable
Yes
Mounting
Symmetrical rail 35 mm (EN 60715)
Housing material
Thermoplastic UL94 V-0
Operating temperature
Tu -40/+85°C
Protection rating
IP20
Failsafe mode
Disconnection from AC network
Disconnection indicator
1 mechanical indicator by pole - Red/Green
Spare module(s)
MDAC1-13VG-320
Remote signaling of disconnection
option DAC1-13VGS-40-320: output on changeover contact
Wiring for remote signaling
1.5 mm² max.
Max. Voltage/Current for remote signaling
250 V / 0.5 A (AC) / 30 V / 3 A (DC)
Dimensions
See diagram - 4TE (EN43880)
Weight
0.593 kg
Standards compliance
IEC 61643-11 / EN 61643-11 / UL1449 ed.5
Certification
KEMA
Thermal disconnector
Internal
Installation ground fault breaker
Type 'S' or delayed
Fuses
Fuse assembly: SFD1-13S-40 /or 125 A min. - 315 A max. - Fuses Type gG