Type 1+2 AC surge protector - 1-pole
DAC1-13VG-40-275
Part Number: 821730214
- Type 1 + 2 + 3 AC surge protector
- VG Technology
- In : 20 kA
- Iimp : 12.5 kA on 10/350µs impulse
- No leakage current
- Pluggable module for each phase
- Remote signaling (option)
- Optimized to TOV
- EN 61643-11, IEC 61643-11 certified
- UL1449 ed.4 compliance
The DAC1-13VG is an extreme duty Type 1+2+3 AC surge protector device designed to protect at the entrance of the electrical installation.
This SPD is particularly useful in a high lightning density area where the risk of heavy surge current or even direct strike is high (eg: buildings equipped with lightning rods).
The DAC1-13VG is one-pole SPD and can be used in common mode or common and differential mode.
DAC1-13VG AC surge protectors are designed to be connected in multi-pole configuration to protect single-phase, 3-phase and 3-phase+Neutral AC networks, sometimes associated with a dedicated N/PE SPD.
Select another reference:
- DAC1-13VG-10-150
- DAC1-13VG-10-275
- DAC1-13VG-10-320
- DAC1-13VG-11-150
- DAC1-13VG-11-275
- DAC1-13VG-11-320
- DAC1-13VG-20-150
- DAC1-13VG-20-275
- DAC1-13VG-20-320
- DAC1-13VG-30-150
- DAC1-13VG-30-275
- DAC1-13VG-30-320
- DAC1-13VG-31-150
- DAC1-13VG-31-275
- DAC1-13VG-31-320
- DAC1-13VG-40-150
- DAC1-13VG-40-275
- DAC1-13VG-40-320
SPD type | 1+2+3 | |
Network | 230/400 V 3-phase+N | |
AC system | TNS | |
Max. AC operating voltage | Uc | 275 Vac |
Temporary Over Voltage (TOV) Charasteristics - 5 sec. | UT | 335 Vac withstand |
Temporary Over Voltage (TOV) Charasteristics - 120 mn | UT | 440 Vac withstand |
Residual Current | Ipe | None |
Follow current | If | None |
Nominal discharge current | In | 20 kA |
Max. discharge current | Imax | 50 kA |
Total Maximum discharge current | Imax Total | 200 kA |
Impulse current by pole | Iimp | 12.5 kA |
Total lightning current | Itotal | 50 kA |
Withstand on Combination waveform IEC 61643-11 | Uoc | 6 kV |
Specific energy by pole | W/R | 40 kJ/ohm |
Protection mode(s) | L/PE and N/PE | |
Protection level L/PE | Up L/PE | 1.5 kV |
Protection level N/PE at 5 kA | Up-5kA | 0.7 kV |
Residual voltage L/PE at 5 kA | Up-5kA | 0.7 kV |
Admissible short-circuit current | Isccr | 50 000 A |
Technology | VG Technology (MOV+ GSG) | |
SPD configuration | 3- phase+Neutral | |
Connection to Network | By screw terminals: 2.5-25 mm² (35 mm² rigid) | |
Format | Plug-in modular box | |
Mounting | Symmetrical rail 35 mm (DIN 60715) | |
Housing material | Thermoplastic UL94 V-0 | |
Operating temperature | Tu | -40/+85°C |
Protection rating | IP20 | |
Failsafe mode | Disconnection from AC network | |
Disconnection indicator | 1 mechanical indicator by pole - Red/Green | |
Spare module(s) | MDAC1-13VG-275 | |
Remote signaling of disconnection | option DAC1-13VGS-40-275: output on changeover contact | |
Wiring for remote signaling | 1.5 mm² max. | |
Max. Voltage/Current for remote signaling | 250 V / 0.5 A (AC) / 30 V / 3 A (DC) | |
Dimensions | See diagram - 4TE (EN43880) |
Standards compliance | IEC 61643-11 / EN 61643-11 / UL1449 4ed. | |
Certification | KEMA / EAC |
Thermal disconnector | Internal | |
Installation ground fault breaker | Type 'S' or delayed | |
Fuses | 125 A min. - 315 A max. - Fuses Type gG |