Type 1+2 PV surge protector - 400 Vdc

DS50PVS-400G/12KT1
Part Number 482942
DS50PVS-400G/12KT1
  • Type 1+2 surge protector for Photovoltaic
  • Impulse currents Iimp/Itotal : 6.25/12.5 kA (10/350µs)
  • Common/Differential mode protection
  • Remote signaling
  • IEC 61643-31, EN 61643-31, EN 50539-11 and UL1449 ed.5 compliance

Type 1 + 2 surge protection (SPD) DS50PV/12KT1 are intended for the protection of photovoltaic power grids. The SPD cartridges are pluggable to ensure quick replacement in the event of a defect. The protection circuit consists of a fault-resistant Y-circuit with a gas discharge tube and high-power varistors. The products are available with a remote signaling system of the state of the surge protectior.

Select another reference:

SPD type
1+2
Network
400 Vdc PV power line
Nominal PV voltage
Uocstc 400 Vdc
Max. PV operating voltage
Ucpv 480 Vdc
Residual Current
Leakage current to Ground
Ipe None
PV Permanent Operating current
Current consumption at Ucpv
Icpv < 0.1 mA
Follow current
If None
Nominal discharge current
15 x 8/20 µs impulses
In 15 kA
Max. discharge current
max. withstand @ 8/20 µs by pole
Imax 40 kA
Total Maximum discharge current
max. total withstand @ 8/20 µs
Imax Total 60 kA
Impulse current by pole
max. withstand 10/350µs by pole
Iimp 6.25 kA
Total lightning current
max. total withstand @ 10/350µs
Itotal 12.5 kA
Current withstand short circuit PV
Iscpv 15 000 A
Connection mode(s)
+/-/PE
Protection mode(s)
Common/Differential mode
Protection level +/-
@ In (8/20µs)
Up 3 kV
Protection level +/PE (-/PE)
@ In (8/20µs)
Up 1.5 kV
Technology
MOV+GDT
Connection to Network
By screw terminals: 2.5-25mm²
Format
Plug-in modular box
Plugable
Yes
Mounting
Symmetrical rail 35 mm (EN 60715)
Housing material
Thermoplastic UL94 V-0
Operating temperature
Tu -40/+85°C
Protection rating
IP20
Outdoor application
No
Disconnection indicator
2 mechanical indicators
Spare module(s)
DSM50PV-400G/12KT1 + DSM50PV-400GPE/12KT1
Remote signaling of disconnection
Output on changeover contact
Dimensions
See diagram
Weight
0.363 kg
Standards compliance
IEC 61643-31 / EN 61643-31 / EN 50539-11 / UL1449 ed.5
Thermal disconnector
Internal
Back-up protection device
Without