Compact single-phase type 2 (or 3) surge protector - Monobloc
Part Number: 70114011
DACN10-21YG-150
- Cost effective single-phase surge protector
- Type 2 or 3 monobloc compact
- In/Imax: 5 kA/10 kA
- Max. load current: 25A
- 2-port configuration (series mounting)
- Remote signaling (option)
- IEC 61643-11 / EN 61643-11 certified
- UL1449 ed.5 compliance
DACN10S AC surge protector is used for the 'secondary' protection of the single-phase networks against the surge voltages creating by lightning.
DACN10S is equipped with an internal thermal safety which will disconnet the unit from the AC network in case of end of life.
Regarding the failsafe mode this surge protector is equipped with the option of disconnection and AC line cut-off. This disconnection will be indicate by the turn on of the red led in the front.
Very compact, the DACN10S surge protector must be installed close by the equipment to protect, downstream a 'primary' surge protector.
DACN10S provides both a common and differential mode protection.
Certificates
|
SPD type
|
IEC | 2+3 |
|
Network
|
120 V single-phase |
|
|
AC system
|
TN |
|
|
Max. AC operating voltage
|
Uc | 150 Vac |
|
Max. load current @25°C
|
IL | 25 A |
|
Temporary Over Voltage (TOV) Characteristics - 5 sec.
Without disconnection
|
UT | 180 Vac withstand |
|
Temporary Over Voltage (TOV) Characteristics - 120 mn
Without disconnection or with safety disconnection
|
UT | 230 Vac disconnection |
|
Residual Current
Leakage current to Ground
|
Ipe | None |
|
Nominal discharge current
15 x 8/20 µs impulses
|
In | 5 kA |
|
Max. discharge current
max. withstand @ 8/20 µs by pole
|
Imax | 10 kA |
|
Withstand on Combination waveform IEC 61643-11
Class III test: 1.2/50µs - 8/20µs
|
Uoc | 10 kV |
|
Protection level L/N
@ In (8/20µs)
|
Up L/N | 0.7 kV |
|
Protection level N/PE
@ In (8/20µs)
|
Up N/PE | 1.5 kV |
|
Protection level L/PE
@ In (8/20µs)
|
Up L/PE | 1.5 kV |
|
Admissible short-circuit current
|
Isccr | 10 000 A |
|
SPD configuration
|
Single phase |
|
|
Connection to Network
|
By screw terminals: 1.5-10mm² |
|
|
Plugable
|
No |
|
|
Mounting
|
Symmetrical rail 35 mm (EN 60715) |
|
|
Housing material
|
Thermoplastic UL94 V-0 |
|
|
Operating temperature
|
Tu | -40/+85°C |
|
Protection rating
|
IP20 |
|
|
Outdoor application
|
No |
|
|
Failsafe mode
|
Disconnection from AC network |
|
|
Disconnection indicator
|
Green LED OFF |
|
|
Remote signaling of disconnection
|
option DACN10S-21YG-275 |
|
|
Dimensions
|
See diagram - 1TE (EN43880) |
|
Standards compliance
|
IEC 61643-11 / EN 61643-11 / UL1449 ed.5 |
|
|
Certification
|
KEMA |
|
Thermal disconnector
|
Internal |
|
|
Installation ground fault breaker
|
Type 'S' or delayed |
|
|
Back-up protection device
|
Fuses type gG - 25A |
Datasheet