Type 2 AC surge protector - 3-phase
DS43-400
DS43-400
Part Number: 461403
  • Type 2 AC Multipolar surge protector
  • In : 20 kA
  • Imax total : 120 kA
  • Pluggable module for each phase
  • Remote signaling option
  • NF EN 61643-11, CEI 61643-11 compliance
  • UL1449 ed.15
Installation Sheet

used mainly for primary protection of single and 3- phase networks at the main electrical panel. They provide common-mode or common and differential mode. This SPD is based on high energy varistor equipped with thermal disconnector and failure indicator, to comply with standards.

The DS40 surge protectors are designed to be used in a multipolar configuration to protect single-phase, 3-phase or 3-phase+Neutral AC networks.They are sometimes associated with dedicated N/PE surge protector based on gas tube technology.



SPD type
following IEC test
2
Network
230/400 V 3-phase
AC system
IT
Nominal line voltage
400 Vac
Max. AC operating voltage L-N
440 Vac
Temporary Over Voltage (TOV) Charasteristics - 5 sec.
without disconnection
580 Vac withstand
Temporary Over Voltage (TOV) Charasteristics - 120 mn
without disconnection or with safety disconnection
770 Vac disconnection
Residual Current
Leakage current to Ground
< 1.5 mA
Operating current
Continious current at Uc
0.5 mA
Follow current
None
Nominal discharge current
15 x 8/20 µs impulses
20 kA
Max. discharge current
max. withstand @ 8/20 µs by pole
40 kA
Total Maximal discharge current
max. total withstand @ 8/20 µs
120 kA
Admissible short-circuit current
25000 A
Connection mode(s)
L/PE
Protection mode(s)
Common mode
Protection level L/PE
@ In (8/20µs)
1.8 kV
Residual voltage at 10 kA
@ 8/20µs
1.5 kV
Residuel voltage at 5 kA
@ 5 kA (8/20µs)
1.3 kV
Technology MOV
SPD configuration 3-phase
Connection to Network By screw terminals: 2.5-25 mm² / by bus
Format
Plug-in modular box
Mounting
Symmetrical rail 35 mm (EN60715)
Housing material Thermoplastic UL94-V0
Operating temperature -40/+85°C
Protection rating IP20
Failsafe behavior Disconnection
Disconnection indicator 1 mechanical indicator by pole
Spare module(s)
DSM40-400
Remote signaling of disconnection
option DS43S-400 : output on changeover contact
Dimensions
See diagram
Certification
UL / CSA /EAC
Standards compliance
IEC 61643-11 / EN 61643-11 / UL1449 4ed.
Thermal disconnector Internal
Fuses
Fuses type gG - 50 A
Installation ground fault breaker Type 'S' or delayed