Type 2 AC surge protector - 3-phase

DS43-120
Part Number: 461603
DS43-120
  • Type 2 AC Multipolar surge protector
  • In : 20 kA
  • Imax total : 120 kA
  • Pluggable module for each phase
  • Remote signaling option
  • EN 61643-11, IEC 61643-11 compliance
  • UL1449 ed.5

used mainly for primary protection of single and 4- phase networks at the main electrical panel. They provide common-mode or common and differential mode. This SPD is based on high energy varistor equipped with thermal disconnector and failure indicator, to comply with standards. The DS40 surge protectors are designed to be used in a multipolar configuration to protect single-phase, 3-phase or 3-phase+Neutral AC networks.They are sometimes associated with dedicated N/PE surge protector based on gas tube technology.

Select another reference:

SPD type
2
Network
120/208 V 3-phase
AC system
TNC
Nominal line voltage
Un 120 Vac
Max. AC operating voltage
Uc 150 Vac
Temporary Over Voltage (TOV) Charasteristics - 5 sec.
Without disconnection
UT 180 Vac withstand
Temporary Over Voltage (TOV) Charasteristics - 120 mn
Without disconnection or with safety disconnection
UT 230 Vac disconnection
Residual Current
Leakage current to Ground
Ipe < 1 mA
Operating current
Continious current at Uc
Ic 0.5 mA
Follow current
If None
Nominal discharge current
15 x 8/20 µs impulses
In 20 kA
Max. discharge current
max. withstand @ 8/20 µs by pole
Imax 40 kA
Total Maximum discharge current
max. total withstand @ 8/20 µs
Imax Total 120 kA
Connection mode(s)
L/PE
Protection mode(s)
Common mode/Differential mode
Residuel voltage at 5 kA
@ 5 kA (8/20µs)
Up-5kA 0.6 kV
Protection level L/PE
@ In (8/20µs)
Up L/PE 1.2 kV
Residual voltage at 10 kA
@ 8/20µs
Up-10kA 0.7 kV
Admissible short-circuit current
Isccr 25 000 A
Technology
MOV
SPD configuration
3-phase
Connection to Network
By screw terminals: 2.5-25mm² / by bus
Format
Plug-in modular box
Mounting
Symmetrical rail 35 mm (EN 60715)
Housing material
Thermoplastic UL94 V-0
Operating temperature
Tu -40/+85°C
Protection rating
IP20
Failsafe mode
Disconnection from AC network
Disconnection indicator
1 mechanical indicator by pole
Spare module(s)
DSM40-120
Remote signaling of disconnection
option DS43S-120 : output on changeover contact
Dimensions
See diagram
Standards compliance
IEC 61643-11 / EN 61643-11 / UL1449 ed.5
Certification
CSA / UL
Thermal disconnector
Internal
Installation ground fault breaker
Type 'S' or delayed
Back-up protection device
Fuses type gG - 50 A