CITEL
Company History
Specialist in overvoltage protection
Locations
Test Facilities
New Range
Service quality
Lightning Surges
Lightning and Transient overvoltages
The origin of overvoltages
Keraunic levels
Effects of lightning
The 'Surge Protector' solution
International Standards
Citel's VG Technology
New Photovoltaic Range : DPVN
CTC Technology
Products
Telecom
Radiocommunication
AC Power
Dataline
Miscellaneous
Photovoltaic
LED
Applications
Toggle Dropdown
Datacenter
LED
Radiocommunication
Security Systems
Industrial Installation
Wind Turbine Installation
Domestic Photovoltaic
Industry Photovoltaic
Solar Farms
Energy storage sytems
Agrivoltaic
Services
Downloading
Webinars
News
Contact
Product ranges
AC Power
Photovoltaic
LED
Telecom
Dataline
Radiocommunication
image/svg+xml
Wind Turbine
Accessories
AC Power
Type 2 AC surge protector
DAC50VG-31-275
Type 2 AC surge protector - 3-phase+N
DAC50VG-31-275
Part Number
821130234
Type 2 + 3 AC surge protector
VG Technology
In: 20 kA
No leakage current
Pluggable module for each phase
Remote signaling (option)
Optimized to TOV
EN 61643-11, IEC 61643-11 certified
UL1449 ed.5 compliance
Datasheet
Installation Sheet
Tender specifications
Contact Us
The pluggable surge protectors Type 2+3 DAC50VG, are designed to protect AC powerline at the main switchboard of the installation. Equipped with the exclusive CITEL’s VG technology, the range achieves an improved protection level and a total absence of leakage current, guaranteeing a maximum protection efficiency, a simplification of use (no additional SPD required) and a maximum lifetime. The surge protectors DAC50VG, are available in multipolar version and in several voltages to protect single or 3-phase networks.
Select another reference:
Electrical Properties
Mechanical Properties
Norms
Deconnector
Schemas
SPD type
2+3
Network
230/400 V 3-phase+N
AC system
TT-TNS
Max. AC operating voltage
Uc
275 Vac
Temporary Over Voltage (TOV) Characteristics - 5 sec.
Without disconnection
UT
335 Vac withstand
Temporary Over Voltage (TOV) Characteristics - 120 mn
Without disconnection or with safety disconnection
UT
440 Vac withstand
Temporary Over Voltage N/PE (TOV HT)
Without disconnection or with safety disconnection
UT
1200 V/300A/200 ms withstand
Residual Current
Leakage current to Ground
Ipe
None
Follow current
If
None
Nominal discharge current
15 x 8/20 µs impulses
In
20 kA
Max. discharge current
max. withstand @ 8/20 µs by pole
Imax
50 kA
Total Maximum discharge current
max. total withstand @ 8/20 µs
Imax Total
50 kA
Withstand on Combination waveform IEC 61643-11
Class III test: 1.2/50µs - 8/20µs
Uoc
6 kV
Connection mode(s)
L/N and N/PE
Protection level
@ In (8/20µs) and @ 6 kV (1,2/50 µs)
Up L/N
1.5 kV
Protection level N/PE
@ In (8/20µs) and @ 6 kV (1,2/50 µs)
Up N/PE
1.5 kV
Residual voltage L/N at 5 kA
@ 5 kA (8/20µs)
Up-5kA
0.7 kV
Protection level N/PE at 5 kA
@ 5 kA (8/20µs)
Up-5kA
0.7 kV
Admissible short-circuit current
Isccr
50 000 A
Network type
AC
Technology
VG Technology (MOV+GSG)
SPD configuration
3-phase+Neutral
Connection to Network
By screw terminals: 2.5-25mm² (35mm² rigid)
Format
Plug-in modular box
Plugable
Yes
Mounting
Symmetrical rail 35 mm (EN 60715)
Housing material
Thermoplastic UL94 V-0
Operating temperature
Tu
-40/+85°C
Protection rating
IP20
Failsafe mode
Disconnection from AC network
Disconnection indicator
1 mechanical indicator by pole - Red/Green
Spare module(s)
MDAC50VG-275+MDAC50G-255
Remote signaling of disconnection
option DAC50VGS-31-275: output on changeover contact
Dimensions
See diagram - 4TE (EN43880)
Standards compliance
IEC 61643-11 / EN 61643-11 / UL1449 ed.5
Certification
KEMA
Thermal disconnector
Internal
Installation ground fault breaker
Type 'S' or delayed
Back-up protection device
50 A min. - 160 A max. - Fuses Type gG
×
Description:
Type 2 AC surge protector - 3-phase+N
Standards compliance:
IEC 61643-11 / EN 61643-11 / UL1449 ed.5
Certification:
KEMA / EAC
Technology:
VG Technology (MOV+GSG)
SPD configuration:
3-phase+Neutral
Remote signaling of disconnection:
option DAC50VGS-31-275: output on changeover contact
SPD type :
2+3
Network:
230/400 V 3-phase+N
AC system:
TT-TNS
Max. AC operating voltage :
275 Vac
Residual Current :
None
Max. discharge current :
50 kA
Total Maximum discharge current :
50 kA
Admissible short-circuit current:
50 000 A
CITEL
Reference:
DAC50VG-31-275
Part Number:
821130234
Or equivalent