Type 1+2+3 AC surge protector - 3-phase+N
DS134VG-230/G
Part Number: 571564
- Type 1 + 2 + 3 AC surge protector
- In : 20 kA
- Iimp total : 50 kA on 10/350µs impulse
- Pluggable module
- Optimized to TOV
- Remote signaling (option)
- EN 61643-11, IEC 61643-11 and UL1449 ed.4 compliance
The DS130VG is an extreme duty Type 1+2+3 AC surge protector device designed to protect at the entrance of the electrical installation.
This SPD is particularly useful in a high lightning density area where the risk of heavy surge current or even direct strike is high (eg: buildings equipped with lightning rods).
The DS130VG is one-pole SPD and can be used in common mode or common and differential mode.
DS130VG AC surge protectors are designed to be connected in multi-pole configuration to protect single-phase, 3-phase and 3-phase+Neutral AC networks, sometimes associated with a dedicated N/PE SPD.
Select another reference:
SPD type | 1+2+3 | |
Network | 230/400 V 3-phase+N | |
AC system | TT-TNS | |
Nominal line voltage | Un | 230 Vac |
Max. AC operating voltage | Uc | 275 Vac |
Temporary Over Voltage (TOV) Charasteristics - 5 sec. | UT | 180 Vac withstand |
Temporary Over Voltage (TOV) Charasteristics - 120 mn | UT | 230 Vac withstand |
Temporary Over Voltage N/PE (TOV HT) | UT | 1200 V/300A/200 ms withstand |
Residual Current | Ipe | None |
Follow current | If | None |
Nominal discharge current | In | 20 kA |
Max. discharge current | Imax | 50 kA |
Impulse current by pole | Iimp | 12.5 kA |
Total lightning current | Itotal | 50 kA |
Withstand on Combination waveform IEC 61643-11 | Uoc | 20 kV |
Withstand on overvoltages IEEE C62.41.1 | 20 kV | |
Specific energy by pole | W/R | 40 kJ/ohm |
Connection mode(s) | L/N and N/PE | |
Protection mode(s) | Common/Differential mode | |
Residual voltage | Up-in | 0.6 kV |
Protection level L/N | Up L/N | 1.25 kV |
Admissible short-circuit current | Isccr | 25000 A |
Technology | VG | |
SPD configuration | 3-phase+Neutral | |
Connection to Network | By screw terminals: 2.5-25 mm² / by bus | |
Format | Plug-in modular box | |
Mounting | Symmetrical rail 35 mm (DIN 60715) | |
Housing material | Thermoplastic UL94 V-0 | |
Operating temperature | Tu | -40/+85°C |
Protection rating | IP20 | |
Failsafe mode | Disconnection | |
Disconnection indicator | 1 mechanical indicator by pole | |
Spare module(s) | DSM130VG-230 | |
Remote signaling of disconnection | option DS134VGS-230/G : output on changeover contact | |
Dimensions | See diagram | |
Weight | 0.498 kg |
Standards compliance | IEC 61643-11 / EN 61643-11 / UL1449 4ed. | |
Certification | UL / EAC / TUV |
Thermal disconnector | Internal | |
Installation ground fault breaker | Type 'S' or delayed | |
Fuses | Fuses Type gG - 125 A |