Type 2 AC surge protector - 3-phase

DU33S-1000/WD
Part Number: 302113
DU33S-1000/WD
  • Type 2 AC Multipolar surge protector
  • In : 15 kA
  • Imax total : 120 kA
  • Remote signaling for each pole
  • NF EN 61643-11, IEC 61643-11 compliance

Used mainly for wind turbines 3- phase networks at the generator and convertor. This type composed of 3-pole DU30S-1000/WD associated with dedicated surge protector DU100G-3500/WD, this module based on gas tube technology to realize protcetion for harmonic interference which mainly appeared in wind turbines. This surge protectors are designed to be used in a multipolar configuration to protect 3-phase AC networks.

Select another reference:

SPD type
2
Network
400/690 Vac 3-phase
AC system
TNC-IT
Nominal line voltage
Un 690 Vac
Max. AC operating voltage
Uc 1000 Vac
Temporary Over Voltage (TOV) Charasteristics - 5 sec.
Without disconnection
UT 1200 Vac withstand
Residual Current
Leakage current to Ground
Ipe None
Operating current
Continious current at Uc
Ic 0.5 mA
Follow current
If None
Nominal discharge current
15 x 8/20 µs impulses
In 15 kA
Max. discharge current
max. withstand @ 8/20 µs by pole
Imax 30 kA
Total Maximum discharge current
max. total withstand @ 8/20 µs
Imax Total 120 kA
Connection mode(s)
L/PE
Protection mode(s)
Common mode/Differential mode
Protection level L/PE
@ In (8/20µs)
Up L/PE 4.2 kV
Admissible short-circuit current
Isccr 25 000 A
Technology
MOV
SPD configuration
3-phase
Connection to Network
By screw terminals: 2.5-25mm² / by bus
Format
Plug-in modular box
Mounting
Symmetrical rail 35 mm (EN 60715)
Housing material
Thermoplastic UL94 V-0
Operating temperature
Tu -40/+85°C
Protection rating
IP20
Failsafe mode
Disconnection from AC network
Disconnection indicator
3 mechanical indicators
Remote signaling of disconnection
output on changeover contact
Wiring for remote signaling
1.5 mm² max.
Max. Voltage/Current for remote signaling
250 V / 0.5 A (AC) / 30 V / 3 A (DC)
Dimensions
See diagram
Standards compliance
EN 61643-11 / IEC 61643-11
Certification
Thermal disconnector
Internal
Installation ground fault breaker
Type 'S' or delayed
Back-up protection device
Fuses type gG - 100A