1-pair DIN rail plug-in Data surge protector
DLAS-48D3
DLAS-48D3
Part Number: 641304
  • Din rail plug-in surge protector
  • 1-pair
  • Visual indicator in failsafe behaviour
  • Un: 48 V
  • Shield wire protection
  • Without line cut-off
  • IEC/EN 61643-21 compliance
  • UL497B approved
Installation Sheet

DLA surge protectors are designed to protect, against surge voltages due to lightning, terminals equipment connected to industrial buses, telecom lines or datalines. These surge protectors must be installed on symmetrical DIN rail and are available for most of the transmission lines: line voltage from 6 to 170V, bitrate up to 10 Mbit/s. These products are 1-pair surge protectors with removable module for easy maintenance.


Select another reference:

Network
RNIS-T0, 48 V line
Nominal line voltage
48 V
Max. DC operating voltage 53 V
Max. load current
300 mA
Max. frequency
> 3 MHz
Insertion loss
< 1 dB
Max. discharge current
max. withstand @ 8/20 µs by pole
20 kA
Line inductance
No
Protection mode(s)
Common/Differential mode
Protection level
@ In (8/20µs)
70 V
Protection level L/N
@ In (8/20µs)
70 V
Impulse current
2 x 10/350µs Test - D1 Category
5 kA
Nominal discharge current
8/20µs Test x 10 - C2 Category
5 kA
Line/Line Nominal discharge current
8/20µs Test x 10 - C2 Category
5 kA
Line/Ground Nominal discharge current
8/20µs Test x 10 - C2 Category
5 kA
line resistance < 4.7 Ohm
 
Technology GDT+Clamping diode+PTC (thermal resistor)
SPD configuration 1-pair + shielded
Connection to Network screw terminal - cross section 0.4-1.5 mm²
Format Plug-in DIN box
Mounting Symmetrical rail 35 mm (EN60715)
Housing material Thermoplastic UL94-V0
Operating temperature -40/+85°C
Protection rating IP20
Failsafe behavior Short-circuit - transmision cut-off - fault mode 3
Disconnection indicator Red light on
Spare module(s)
DLASM-48D3
Dimensions
See diagram
Standards compliance IEC 61643-21 / EN 61643-21 / UL497B
Certification UL / EAC