Compact Type 2 hard wired surge protector

MLPCA1-230L-2L
Part Number 835265
MLPCA1-230L-2L
  • Type 2 (or 3) 2 phase + N surge protector
  • Compact
  • Wall mounting
  • Status indicators
  • IP65
  • AC disconnection in case of end of life

MSB10 surge protectors Type 2 (or 3) are designed for effective protection of sensitive equipment, in addition to the surge protector installation (coordination surge protector). These surge protectors utilize a compact and economica scheme based varistors, to obtain a power flow relevant for secondary protection.

Select another reference:

SPD type
2+3
Network
220-240V 2-phase + N
AC system
TT-TN
Nominal line voltage
Un 230 V
Max. AC operating voltage
Uc 320 Vac
Max. load current
@25°C
IL 10 A
Temporary Over Voltage (TOV) Characteristics - 5 sec.
Without disconnection
UT 335 Vac withstand
Temporary Over Voltage (TOV) Characteristics - 120 mn
Without disconnection or with safety disconnection
UT 440 Vac disconnection
Operating current
Continious current at Uc
Ic < 1 mA
Follow current
If None
Nominal discharge current
15 x 8/20 µs impulses
In 5 kA
Max. discharge current
max. withstand @ 8/20 µs by pole
Imax 10 kA
Total Maximum discharge current
max. total withstand @ 8/20 µs
Imax Total 30 kA
Withstand on Combination waveform IEC 61643-11
Class III test: 1.2/50µs - 8/20µs
Uoc 10 kV
Withstand on overvoltages IEEE C62.41.1
10 kV / 10 kA
Protection mode(s)
Common/Differential mode
Protection level
@ In (8/20µs)
Up 1.5 kV
Protection level L/N
@ In (8/20µs)
Up L/N 1.5 kV
Protection level L/PE
@ In (8/20µs)
Up L/PE 1.5 kV
Admissible short-circuit current
Isccr 10 000 A
Technology
MOV+GDT
Connection to Network
Cable with 5-wire of 1.5mm²
Mounting
Wall or plate
Housing material
Thermoplastic UL94 V-0
Operating temperature
Tu -40/+85°C
Protection rating
IP65
Failsafe mode
Disconnection and AC line cut-off
Disconnection indicator
LED green OFF and AC network cut-off
Voltage/operating indicator
Green Led ON
Dimensions
See diagram
Weight
0.152 kg
Standards compliance
IEC 61643-11 / EN 61643-11 / UL1449 ed.5
Thermal disconnector
Internal
Installation ground fault breaker
Type 'S' or delayed