Surge protector for LED lighting system Class 1
DLPM1-230L
DLPM1-230L
Part Number: 355913
  • Type 2 (or 3) surge protectors for LED classe I
  • Mechanical status indicator
  • Very compact (low profile)
  • DIN rail mounting
  • Screw terminal connection
  • AC line Disconnection in end of life
  • EN 61643-11 compliance
Installation Sheet

The DLPM range is a series of DIN-mount AC surge protector designed to be installed inside the cutouts: his compact size and lower height make it compatible with the DIN rail mounting of its enclosures. This range has a mechanical disconnect indicator.

Select another reference:

SPD type 2 (ou 3)
Network 220-240 V single-phase
AC system TT/TN
Nominal line voltage Un 230-277 Vac
Max. AC operating voltage L-N Uc 320 Vac
Max. load current IL 10 A
Temporary Over Voltage (TOV) Charasteristics - 5 sec. UT 335 Vac withstand
Temporary Over Voltage (TOV) Charasteristics - 120 mn UT 440 Vac disconnection
Temporary Over Voltage N/PE (TOV HT) UT 1200 V/300A/200 ms disconnection
Residual Current Ipe None
Nominal discharge current In 5 kA
Max. discharge current Imax 10 kA
Total Maximal discharge current Imax Total 20 kA
Withstand on Combination waveform IEC 61643-11 Uoc 10 kV / 5 kA
Withstand on overvoltages IEEE C62.41.1 10 kV / 10 kA
Protection mode(s) Common/Differential mode
Protection level Up 1.5 kV
Protection level L/N Up L/N 1.5 kV
Protection level L/PE Up L/PE 1.5 kV
Protection level CM/DM Up mc/md 1.5/1.5 kV
Admissible short-circuit current Isccr 10 000 A
Technology MOV+GDT
Connection to Network Screw terminal 2.5 mm² max. Earthing conductor 2 mm² - length 60 cm
Mounting Symmetrical rail 35 mm (EN60715)
Housing material Thermoplastic UL94-V0
Operating temperature -40/+85°C
Protection rating IP20
Failsafe mode AC network cutt-off
Disconnection indicator Red Indicator + AC line disconnection
Voltage/operating indicator Green Indicator
Remote signaling of disconnection No
Dimensions See diagram
Standards compliance EN 61643-11 / IEC 61643-11
Certification UL / EAC / TUV