Type 1+2+3 AC surge protector - 3-phase+N
DS254VG-400
DS254VG-400
Part Number: 2581
  • Type 1+2+3 unipolar surge protector
  • 25 kA on 10/350µs impulse
  • Low voltage Up
  • Internal disconnection, status indicator and remote signaling
  • Optimized to TOV
  • IEC 61643-11 compliance
  • UL1449 ed.4 recognition
Installation Sheet

The DS250VG is an extreme duty Type 1+2+3 AC surge protector device designed to protect at the entrance of the electrical installation. This SPD is particularly useful in a high lightning density area where the risk of heavy surge current or even direct strike is high (eg: buildings equipped with lightning rods). The DS250VG is one-pole SPD and can be used in common mode or common and differential mode.

DS250VG AC surge protectors are designed to be connected in multi-pole configuration to protect single-phase, 3-phase and 3-phase+Neutral AC networks, sometimes associated with a dedicated N/PE SPD.



SPD type
following IEC test
1+2+3
Network
230/400 V 3-phase+N
AC system
IT-TNS
Nominal line voltage
400 Vac
Max. AC operating voltage L-N
440 Vac
Max. load current
100 A
Temporary Over Voltage (TOV) Charasteristics - 5 sec.
without disconnection
580 Vac withstand
Temporary Over Voltage (TOV) Charasteristics - 120 mn
without disconnection or with safety disconnection
770 Vac withstand
Residual Current
Leakage current to Ground
None
Operating current
Continious current at Uc
None
Follow current
None
Nominal discharge current
15 x 8/20 µs impulses
30 kA
Max. discharge current
max. withstand @ 8/20 µs by pole
70 kA
Impulse current by pole
max. withstand 10/350µs by pole
25 kA
Total lightning current
max. total withstand @ 10/350µs
100 kA
Withstand on Combinaison waveform IEC 61643-11
Class III test: 1.2/50µs - 8/20µs
6 kV
Withstand on overvoltages IEEE C62.41.1
20 kV
Admissible short-circuit current
50000 A
Connection mode(s)
L/PE and N/PE
Protection mode(s)
Common mode
Residual voltage
@ In (8/20 µs)
1.1 kV
Protection level L/PE
@ In (8/20µs)
1.5 kV
Specific energy by pole
max. withstand 10/350 µs
156 kJ/ohm
Technology VG
SPD configuration 3-phase+Neutral
Connection to Network By screw terminals : 6-35 mm² / by bus
Format
1-pole modular box assembled
Mounting
Symmetrical rail 35 mm (EN60715)
Housing material Thermoplastic UL94-V0
Operating temperature -40/+85°C
Protection rating IP20
Failsafe behavior Disconnection
Disconnection indicator 1 mechanical indicator by pole
Remote signaling of disconnection
Output on changeover contact
Dimensions
See diagram
Certification
EAC
Standards compliance
IEC 61643-11 / EN 61643-11 / UL1449 4ed.
Thermal disconnector Internal
Installation ground fault breaker Type 'S' or delayed
Fuses
Fuses type gG - 315 A