Surge and Electrostactic protector for Class II LED lighting system
MLPC2-230L-R/ESP2
MLPC2-230L-R/ESP2
Part Number: 832217
  • Type 2 (or 3) Surge & Electrostatic protectors
  • For Class II Led lighting
  • Improved coordination with internal MOV
  • Electrostatic protection included
  • Comply class II safety rules
  • Very compact
  • Plate mounting
  • Spring terminal connection
  • Status indicator
  • End of life AC Disconnection
  • IEC 61643-11 and EN 61643-11 compliance
Installation Sheet



SPD type
follow test IEC 61643-11
2/3
Network
220-240 V single-phase
AC system
TT/TN
Nominal line voltage
220-240 Vac
Max. AC operating voltage L-N 320 Vac
Max. load current
5 A
Temporary Over Voltage (TOV) Charasteristics - 5 sec.
without disconnection
335 Vac withstand
Temporary Over Voltage (TOV) Charasteristics - 120 mn
without disconnection or with safety disconnection
440 Vac disconnection
Residual Current
Leakage current to Ground
none
Nominal discharge current
15 x 8/20 µs impulses
5 kA
Max. discharge current
max. withstand @ 8/20 µs by pole
10 kA
Withstand on Combinaison waveform IEC 61643-11
Class III test: 1.2/50µs - 8/20µs
10 kV/5 kA
Withstand on overvoltages IEEE C62.41.1 10 kV/10 kA
Admissible short-circuit current 10000 A
Protection level
@ In (8/20µs)
1.5 kV
Electrostatic protection level >0.5 kV
Electrostatic protection mode N/Functional Earth
 
Connection to Network 2 screw terminals opposite side in/out - wire 2.5 mm² max.
Mounting on plate
Housing material Thermoplastic UL94-V0
Operating temperature -40/+85°C
Protection rating IP20
Failsafe behavior Disconnection and AC line cut-off
Disconnection indicator Led green OFF and AC network cut-off
Voltage/operating indicator Green Led ON
Remote signaling of disconnection no
Dimensions
see diagram
Standards compliance EN 61643-11 / IEC 61643-11
Certification EAC
Thermal disconnector internal
Installation ground fault breaker Type 'S' or delayed