Compact single-phase type 2 (or 3) surge protector - 230 V - Monobloc
DACN10-L11-150
Part Number: 70112011
- Cost effective single-phase surge protector
- Type 2+3 monobloc compact
- In/Imax: 5 kA/10 kA
- Max. load current: 16A
- Disconnection + AC line cut
- 2-port configuration (series mounting)
- Remote signaling (option)
- EN 61643-11, IEC 61643-11 compliance
DACN10-L AC surge protector is used for the 'secondary' protection of the single-phase networks against the surge voltages creating by lightning.
DS98 is equipped with in-line safety disconnectin and double output connection.
The disconnection will be indicate by the turn on of the red led in the front.
Very compact, the DS98L surge protector must be installed close by the equipment to protect, downstream a 'primary' surge protector.
DACN10-L provides both a common and differential mode protection.
Select another reference:
SPD type | 2+3 | |
Network | 120 Vac single-phase | |
AC system | TT-TN | |
Max. AC operating voltage | Uc | 150 Vac |
Max. load current | IL | 16 A |
Temporary Over Voltage (TOV) Charasteristics - 5 sec. | UT | 180 Vac withstand |
Temporary Over Voltage (TOV) Charasteristics - 120 mn | UT | 230 Vac disconnection |
Temporary Over Voltage N/PE (TOV HT) | UT | 1200 V/300A/200 ms breaker disconnection |
Residual Current | Ipe | None |
Nominal discharge current | In | 5 kA |
Max. discharge current | Imax | 10 kA |
Withstand on Combination waveform IEC 61643-11 | Uoc | 10 kV |
Protection level L/N | Up L/N | 0.7 kV |
Protection level N/PE | Up N/PE | 1.5 kV |
Admissible short-circuit current | Isccr | 10 000 A |
SPD configuration | Single phase | |
Connection to Network | by screw terminals: 1.5-10mm² | |
Mounting | Symmetrical rail 35 mm (EN60715) | |
Housing material | Thermoplastic UL94 V-0 | |
Operating temperature | Tu | -40/+85°C |
Protection rating | IP20 | |
Failsafe mode | Disconnection and AC line cut-off | |
Disconnection indicator | Green led OFF | |
Remote signaling of disconnection | option DACN10S-L11-150 | |
Dimensions | See diagram - 1TE (DIN43880) | |
Weight | 0.090 kg |
Standards compliance | IEC 61643-11 / EN 61643-11 / UL1449 4ed. |
Thermal disconnector | Internal | |
Installation ground fault breaker | Type 'S' or delayed | |
Fuses | Fuses type gG - 25A |