Type 1+2 AC surge protector - 1-pole
DAC1-13VG-40-275
DAC1-13VG-40-275
Part Number: 821730214
  • Type 1 + 2 + 3 AC surge protector
  • VG Technology
  • In : 20 kA
  • Iimp : 12.5 kA on 10/350µs impulse
  • No leakage current
  • Pluggable module for each phase
  • Remote signaling (option)
  • Optimized to TOV
  • EN 61643-11, IEC 61643-11 and UL1449 ed.4 compliance
Installation Sheet Range Technical Sheet

The DAC1-13VG is an extreme duty Type 1+2+3 AC surge protector device designed to protect at the entrance of the electrical installation. This SPD is particularly useful in a high lightning density area where the risk of heavy surge current or even direct strike is high (eg: buildings equipped with lightning rods). The DAC1-13VG is one-pole SPD and can be used in common mode or common and differential mode. DAC1-13VG AC surge protectors are designed to be connected in multi-pole configuration to protect single-phase, 3-phase and 3-phase+Neutral AC networks, sometimes associated with a dedicated N/PE SPD.


SPD type 1+2+3
Network 230/400 V 3-phase+N
AC system TNS
Max. AC operating voltage L-N Uc 275 Vac
Temporary Over Voltage (TOV) Charasteristics - 5 sec. UT 335 Vac withstand
Temporary Over Voltage (TOV) Charasteristics - 120 mn UT 440 Vac withstand
Residual Current Ipe None
Follow current If None
Nominal discharge current In 20 kA
Max. discharge current Imax 50 kA
Total Maximal discharge current Imax Total 200 kA
Impulse current by pole Iimp 12.5 kA
Total lightning current Itotal 50 kA
Withstand on Combination waveform IEC 61643-11 Uoc 6 kV
Specific energy by pole W/R 40 kJ/ohm
Protection mode(s) L/PE and N/PE
Protection level L/PE Up L/PE 1.5 kV
Protection level N/PE at 5 kA Up-5kA 0.7 kV
Residual voltage L/PE at 5 kA Up-5kA 0.7 kV
Admissible short-circuit current Isccr 50 000 A
Technology VG
SPD configuration 3- phase+Neutral
Connection to Network By screw terminals: 2.5-25 mm² (35 mm² rigid)
Format Plug-in modular box
Mounting Symmetrical rail 35 mm (EN60715)
Housing material Thermoplastic UL94-V0
Operating temperature -40/+85°C
Protection rating IP20
Failsafe mode Disconnection from AC network
Disconnection indicator 1 mechanical indicator by pole - Red/Green
Spare module(s) MDAC1-13VG-275
Remote signaling of disconnection option DAC1-13VGS-40-275: output on changeover contact
Wiring for remote signaling 1.5 mm² max.
Maw. Voltage/Current for remote signaling 250 V / 0.5 A (AC) / 30 V / 3 A (DC)
Dimensions See diagram - 4TE (EN43880)
Standards compliance IEC 61643-11 / EN 61643-11 / UL1449 4ed.
Certification IEC 61463-11 / EN 61643-11