Surge protectors for LED lighting system Class 2
MLP2-230L-P/DL
Part Number: 721232
  • Type 2 or 3 surge protector for 2-phase (Power/Control)
  • For LED lighting system
  • Class I configuration
  • IP65 version
  • Very compact dimensions
  • Max. discharge current 10kA
  • EN 61643-11, IEC 61643-11 compliance

The MLP range is a comprehensive series of AC surge protectors dedicated to LED lighting system. Some versions are equipped with an extra dataline surge protection (RS485 or DALI) in order to provide a full solution for LED systems with transmission features. By this way the MLP range is able to provide all the existing configurations with an efficient solution . MLP surge protectors are based on a powerful association of MOV and GDT components, able to protect LED system against huge surges without disconnection. In the worse case, the SPD will fail in safety condition. Indication of the SPD failure is performed through power supply cut off and/or through remote signaling feature.


SPD type 2+3
AC system TT-TN
Nominal line voltage Un 230-277 Vac
Max. AC operating voltage L-N Uc 305 Vac
Max. frequency f max. 10 MHz
Max. load current IL 2.5 A
Temporary Over Voltage (TOV) Charasteristics - 5 sec. UT 335 Vac withstand
Temporary Over Voltage (TOV) Charasteristics - 120 mn UT 440 Vac disconnection
Residual Current Ipe None
Follow current If None
Nominal discharge current In 5 kA
Max. discharge current Imax 10 kA
Total Maximum discharge current Imax Total 20 kA
Withstand on Combination waveform IEC 61643-11 Uoc 10 kV / 5 kA
Withstand on overvoltages IEEE C62.41.1 10 kV / 10 kA
Protection level L/N Up L/N 1.5 kV
Protection level L/PE Up L/PE 1.5 kV
Admissible short-circuit current Isccr 10000 A
Mounting Wall or plate
Housing material Thermoplastic UL94-V0
Operating temperature Tu -40/+85°C
Dimensions See diagram
Standards compliance IEC 61643-11 / EN 61643-11 / UL1449 4ed.
Thermal disconnector Internal
Installation ground fault breaker Type 'S' or delayed