Gas filed Spark Gap (GSG) for Surface Mounting
BG 600V
BG 600V
Part Number: 90130076
  • Bi-polar
  • GSG (Gas filled Spark Gap)
  • No radioactive
  • High energy
CITEL_Certif_ROHS_BG_BF_BHDGA.pdf

CITEL has developed a specific technology : GSG. These component are designed to be used on an AC network: they have an increased extinction capability and a higher current discharge capability with either a 8/20µs or 10/350µs waveform.

Select another reference:

Follow current If Yes
Follow current interrupting capability Ifi > 100 A
Nominal discharge current In 60 kA
Total Maximal discharge current Imax Total 100 kA
Total lightning current Itotal 15 kA
DC sparkover voltage (100V/s) 450-750 V
Insulation resistance ≥10 GOhms
Maximum impulse sparkover voltage (1kV/µs) <1500 V
Impulse sparkover voltage (100V/µs) -
DC Holdover voltage >60 V
Operating and storage temperature -40°C / +90°C
Dimensions See diagram
Weight -
Standards compliance UIT-T-K12 rec. / IEC 61643-11 / IEC 61643-311
Certification ROHS / REACH